Overview : Level 3 — Register Mapping
- The GCAN-205 is an industrial Modbus TCP Slave-to-CAN Gateway that connects Modbus TCP-based PLCs and industrial Ethernet systems with CAN bus devices through configurable register mapping.
- It allows a Modbus TCP master to read received CAN data from mapped registers and write data to mapped registers for CAN frame transmission. Supporting CAN 2.0A/B, 10/100 Mbps Ethernet, and 1500 V DC CAN isolation, the GCAN-205 provides a practical solution for integrating CAN devices into Modbus TCP-based automation systems.
GCAN-205: 1-Channel Ethernet (Modbus TCP) to CAN Protocol Converter
Modbus TCP Slave to CAN Gateway
Level 3 Gateway: Register Mapping
Designed for seamless industrial protocol conversion
1x Ethernet (RJ45) and 1x CAN 2.0A/2.0B interface
1500V DC isolation on CAN side
Operating Temp. at -40°C to +85°C
Free config software with zero programming.
1. Level 3 Gateway: Register Mapping
Maps CAN frames to Modbus registers through configurable mapping tables, enabling structured data exchange between Modbus TCP and CAN networks.
2. Modbus TCP Slave for PLC Integration
Works as a Modbus TCP slave, allowing PLCs and other Modbus TCP master devices to access CAN data through standard Modbus function codes.
3. CAN-to-Modbus TCP Data Acquisition
Receives CAN frames and stores their data in mapped Modbus registers, allowing a PLC or Modbus TCP master to read CAN network data.
4. Modbus TCP-to-CAN Frame Transmission
Converts data written to mapped Modbus registers into CAN frames, supporting both event-triggered and cyclic transmission modes.
5. Flexible CAN Register Mapping
Supports up to 32 mapping groups in each direction, with configurable CAN IDs, frame formats, data lengths and Modbus register addresses.
6. CAN 2.0A/B Protocol Support
Supports standard and extended CAN frames with configurable baud rates from 5 kbit/s to 1 Mbit/s, covering a wide range of CAN-based devices.
7. 10/100 Mbps Ethernet Interface
Provides an RJ45 Ethernet connection with automatic speed negotiation, supporting integration into standard industrial Ethernet networks.
8. 1500 V DC CAN Electrical Isolation
Provides electrical isolation on the CAN interface to help protect the gateway and improve communication reliability in industrial environments.
9. Industrial DIN-Rail Design
Features compact DIN-rail mounting, an embedded hardware watchdog and an operating temperature range of -40°C to +85°C for industrial installations.
Find Your Gateway Solution by Application
◆ Application 1: PLC-Based CAN Device Data Acquisition
💡 How it works:
- Role: Acts as a Modbus TCP Slave, providing CAN bus data to a PLC or other Modbus TCP master.
- Connection: Connects a CAN network to a PLC through an Ethernet interface.
- Data Processing: Receives and buffers CAN frames, maps the data to Modbus registers, and makes it available for the PLC to read.
◆ Application 2: PLC-Based CAN Device Command Transmission
💡 How it works:
- Role: Acts as a communication gateway, converting Modbus TCP commands into CAN frames.
- Connection: Connects a Modbus TCP master, such as a PLC, to CAN-based controllers or other devices.
- Data Processing: Converts data written to mapped Modbus registers into CAN frames, which can be transmitted in trigger-based or cyclic mode.
◆ Application 3: Integrating CAN Devices into Industrial Ethernet Systems
💡 How it works:
- Role: Acts as a Modbus TCP Slave-to-CAN gateway, enabling data exchange between Ethernet-based control systems and CAN networks.
- Connection: Connects the Ethernet network to CAN devices through its RJ45 Ethernet port and CAN interface.
- Data Processing: Uses configurable mapping tables to transfer selected CAN data to Modbus registers and convert Modbus register data into CAN frames.
Semantic Processing Tier and Core Capability & Target Models of Gateways
Gateway Selection Guide: Semantic Depth & Master/Slave Capability
| Model | Semantic Processing Level | CAN-Side Role | Can it act as a Master? | Sub-models / Programmability | Interfaces | Application | |
| GCAN-204 | Register mapping (Not transparent) | Fixed Modbus RTU Slave | No. Modbus RTU Slave only. | Single fixed firmware. Free config software, zero programming. | 1× RS485, 1× CAN 2.0A/B |
PLC/HMI (Modbus master) reading CAN sensors; legacy retrofits. | |
| GCAN-205 | Register mapping (Not transparent). | Fixed Modbus TCP Slave | No. Modbus TCP Slave only. | Single fixed firmware. Free config software. | 1× Ethernet, 1× CAN 2.0A/B |
SCADA/HMI reading CAN devices over Ethernet. | |
| GCAN-208 | Pure physical-layer passthrough. | No protocol role | No. No protocol stack. | Sub-models: 208-1, 208-2, 208-2F. | 1–2× Fiber, 1–2× CAN 2.0A/B |
Long-distance CAN extension, high EMI isolation. | |
|
Socket-level transparent transmission. | No protocol role | No. Data pipe only. | Single unit. Can work in pairs as a wireless CAN repeater. | 2× CAN, 1× Ethernet, 1× WiFi |
Wireless CAN access, mobile debugging. | |
| GCAN-212B | Socket-level transparent transmission. | No protocol role | No. Data pipe only. | Single unit (DIN-rail). | 2× CAN, 1× Ethernet |
Dual-channel CAN to Ethernet inside cabinets. | |
| GCAN-GT-8221 | Splits by sub-model: | EtherCAT Slave → CAN: |
|
Sub-models: -CAN, -COM. Fixed firmware. | 2× EtherCAT (daisy-chain), 1× CAN |
EtherCAT PLC integrating existing CANopen slave devices. | |
| • -CAN: Raw passthrough. | • -CAN: Passthrough | ||||||
| • -COM: CANopen slave stack (Semantic parsing). | • -COM: CANopen Slave | ||||||
| GCAN-GT-8321 | Splits by sub-model (Most comprehensive): | Profinet Slave → CAN: | Profinet side: No. | Sub-models: -CAN, -COM, -COS, -MRTUM, -MRTUS, -MTCPS, -PROG. | 2× Profinet, 1× CAN, 1× RS485, 1× Ethernet (varies) |
Siemens PLC integrating CANopen drives; active CANopen network management. | |
| • -CAN: Raw passthrough. | • -CAN: Passthrough | CAN side: NO | |||||
| • -COM: CANopen Slave. | • -COM: CANopen Slave | CAN side: NO | |||||
| • -COS: CANopen Master (NMT, node monitoring). | • -COS: CANopen Master | CAN side: -COS YES | |||||
| • -PROG: Programmable. | User-defined (Master/Slave configurable) | Yes (Configurable via program) | |||||
| GCAN-GT-415 | Full programmable semantic processing. | Configurable via program | Yes, fully configurable. CANopen & Modbus Master/Slave. | No fixed sub-models. Programmable via OpenPCS (IEC 61131-3). | 2× CAN, Ethernet, RS485, RS232, 4G, WiFi | Multi-protocol mixing, non-standard logic, remote upload (acts as a mini-PLC). |
GCAN-205 Technical FAQ: Modbus TCP Slave to CAN Integration & Troubleshooting
Q How do I choose the right CAN gateway based on my system architecture and development needs? ▼
You should choose based on how you want your host system to process the CAN data:
Scenario A: I want to build custom software and process raw CAN frames myself.
👉 Choose GCAN-212 (Transparent Gateway). It provides a raw TCP/UDP pipeline (via Socket API), allowing you to define your own application layer protocol and ports.
Scenario B: I need zero-code integration for a Serial (RS485) PLC or SCADA.
👉 Choose GCAN-204 (Modbus RTU to CAN). It maps CAN data directly to Modbus registers, allowing serial masters to read/write without any programming.
Scenario C: I need zero-code integration for an Ethernet PLC or SCADA system.
👉 Choose GCAN-205 (Modbus TCP to CAN). It acts as a standard Modbus TCP Slave, seamlessly bridging CAN networks to your Ethernet infrastructure.
Q Why doesn't this Modbus TCP to CAN gateway (GCAN-205) support raw Socket APIs or a transparent passthrough mode? ▼
The GCAN-205 is specifically designed to be a Modbus TCP Slave for maximum stability in OT (Operational Technology) environments. It encapsulates the Modbus protocol stack and focuses entirely on Semantic Register Mapping. By strictly adhering to standard Modbus TCP, it ensures plug-and-play compatibility with PLCs (like Siemens, Mitsubishi) and SCADA software. If you need to build custom software and process raw CAN frames via Socket APIs, the GCAN-212 transparent gateway is the correct choice.
Q Why is the TCP port of GCAN-205 fixed at 502? Can I change it to a custom port like 4001? ▼
No, the port cannot be changed. The 502 port is the officially assigned standard port for the Modbus TCP protocol.
To clarify the network layers: HTTP and Modbus TCP are both Application Layer protocols, but they use different designated ports (80 for HTTP, 502 for Modbus TCP). By locking the port at 502, GCAN-205 guarantees automatic discovery by standard Modbus TCP Masters. If you need to build a custom application layer protocol using arbitrary ports (e.g., 4001), you should choose the GCAN-212, which provides a raw TCP pipeline.
Q How does the Modbus TCP polling architecture affect real-time performance compared to a transparent gateway? ▼
- GCAN-205 (Modbus TCP Mode) operates on a Master-Slave polling mechanism. The PLC must actively send read requests to fetch the latest CAN data from the registers. The update rate depends on the PLC's scan cycle and network latency. This is highly stable for standard industrial control (tolerating tens of milliseconds of latency).
- Transparent Gateways (e.g., GCAN-212) are event-driven. Raw CAN data is pushed directly to the host software as soon as it arrives. For high-frequency, microsecond-level synchronization, the transparent mode is more suitable.
Q Can I connect multiple GCAN-205 modules to a single Ethernet PLC or SCADA system? ▼
Yes. Although the TCP port is fixed at 502, each module has a unique IP address. Your PLC or SCADA (acting as the Modbus TCP Master) can establish simultaneous TCP connections to multiple modules (e.g., 192.168.1.10:502, 192.168.1.11:502), allowing you to expand your CAN networks across different segments.
Q What happens if the CAN bus disconnects or an Ethernet cable is unplugged? ▼
- If the Ethernet drops: GCAN-205 supports TCP auto-reconnect. It will automatically try to restore the TCP link to ensure reliable data recovery when the network returns.
- If the CAN node goes offline: The mapped Modbus registers will simply hold their last known values. We recommend implementing a heartbeat (alive counter) logic in your CAN nodes. If your PLC reads the same heartbeat value for too long, it can trigger a system alarm.
Q Can the GCAN-205 act as a Modbus TCP Master or bridge two CAN buses? ▼
No. The GCAN-205 is strictly a Modbus TCP Slave device designed for Ethernet-to-CAN conversion. It cannot initiate Modbus TCP requests to other devices, nor can it directly bridge two CAN buses together.