Overview : Level 3 — Register Mapping
- The GCAN-204 is an industrial Modbus RTU Slave to CAN gateway, enabling bidirectional data exchange between Modbus RTU master devices and CAN networks.
- It maps CAN data to Modbus registers, allowing PLCs, HMIs and other Modbus RTU master devices to read CAN data and send data to CAN devices through standard Modbus commands.
- With configurable data mapping and communication parameters, the GCAN-204 simplifies integration between Modbus RTU-based control systems and CAN-connected devices.
The GCAN-204 is an industrial Modbus RTU slave to CAN gateway with RS485 and CAN interfaces, designed for DIN-rail mounting and protocol conversion between an existing Modbus master and CAN devices.
Modbus RTU Slave to CAN Gateway
Level 3 Gateway: Register Mapping
Designed for seamless industrial protocol conversion
1x RS485 and 1x CAN 2.0A/2.0B interface
1500V DC isolation on CAN side
Operating Temp. at -40°C to +85°C
Free config software with zero programming.
01. Modbus RTU Slave Operation
Operates exclusively as a Modbus RTU Slave, responding to requests from an external Modbus master such as a PLC or HMI. It does not support active Modbus device polling.
02. Passive CAN Data Acquisition
Receives and buffers CAN bus data, making it available for the Modbus master to read through mapped registers.
03. Modbus-to-CAN Data Transmission
Allows the Modbus master to write data to mapped registers, triggering transmission of corresponding data to the CAN network.
04. Configurable Register Mapping
Configures the mapping between CAN data and Modbus registers to match application requirements.
05. Standard Modbus Function Codes
Supports Modbus RTU function codes 03H, 04H, 06H and 16H for register reading and writing.
06. CAN 2.0A/B Compatibility
Supports standard CAN 2.0A and 2.0B communication, with configurable baud rates from 5 kbps to 1 Mbps.
07. Data Conversion Throughput
Supports data conversion at up to 400 CAN frames per second for Modbus-CAN communication.
08. PC-Based Software Configuration
Configure communication parameters and data mapping through dedicated Windows configuration software. Settings are stored in non-volatile memory.
09. Industrial Power Supply & Isolation
Operates on a 9–24 V DC power supply and provides 1500 V DC electrical isolation between communication interfaces.
Find Your Gateway Solution by Application
◆ Application 1: PLC-Based CAN Device Data Acquisition
💡 How it works:
- Role: Acts as a Modbus RTU Slave, providing CAN bus data to a PLC or other Modbus RTU master.
- Connection: Connects the CAN network to a PLC through the Modbus RTU communication interface.
- Data Processing: Receives and buffers CAN frames, maps the data to Modbus registers, and makes it available when requested by the PLC.
◆ Application 2: PLC-to-CAN Device Command Transmission
💡 How it works:
- Role: Serves as a communication bridge for transmitting PLC commands to CAN-connected devices.
- Connection: The PLC writes data to the GCAN-204 through Modbus RTU, while the gateway connects to the target CAN devices.
- Signal Transmission: Converts the mapped Modbus register data into CAN frames and transmits them to the CAN network.
◆ Application 3: CAN Device Integration into Modbus RTU Automation Systems
💡 How it works:
- Role: Integrates CAN-based equipment into existing Modbus RTU-based automation systems.
- Connection: Connects CAN devices to a PLC or HMI through the GCAN-204 and Modbus RTU communication.
- Data Processing: Maps CAN data to Modbus registers, allowing the host system to access CAN device data using standard Modbus RTU commands.
Gateway Selection Guide: Semantic Depth & Master/Slave Capability
| Model | Semantic Processing Level | CAN-Side Role | Can it act as a Master? | Sub-models / Programmability | Interfaces | Application | |
| GCAN-204 | Register mapping (Not transparent) | Fixed Modbus RTU Slave | No. Modbus RTU Slave only. | Single fixed firmware. Free config software, zero programming. | 1× RS485, 1× CAN 2.0A/B |
PLC/HMI (Modbus master) reading CAN sensors; legacy retrofits. | |
| GCAN-205 | Register mapping (Not transparent). | Fixed Modbus TCP Slave | No. Modbus TCP Slave only. | Single fixed firmware. Free config software. | 1× Ethernet, 1× CAN 2.0A/B |
SCADA/HMI reading CAN devices over Ethernet. | |
| GCAN-208 | Pure physical-layer passthrough. | No protocol role | No. No protocol stack. | Sub-models: 208-1, 208-2, 208-2F. | 1–2× Fiber, 1–2× CAN 2.0A/B |
Long-distance CAN extension, high EMI isolation. | |
|
Socket-level transparent transmission. | No protocol role | No. Data pipe only. | Single unit. Can work in pairs as a wireless CAN repeater. | 2× CAN, 1× Ethernet, 1× WiFi |
Wireless CAN access, mobile debugging. | |
| GCAN-212B | Socket-level transparent transmission. | No protocol role | No. Data pipe only. | Single unit (DIN-rail). | 2× CAN, 1× Ethernet |
Dual-channel CAN to Ethernet inside cabinets. | |
| GCAN-GT-8221 | Splits by sub-model: | EtherCAT Slave → CAN: |
|
Sub-models: -CAN, -COM. Fixed firmware. | 2× EtherCAT (daisy-chain), 1× CAN |
EtherCAT PLC integrating existing CANopen slave devices. | |
| • -CAN: Raw passthrough. | • -CAN: Passthrough | ||||||
| • -COM: CANopen slave stack (Semantic parsing). | • -COM: CANopen Slave | ||||||
| GCAN-GT-8321 | Splits by sub-model (Most comprehensive): | Profinet Slave → CAN: | Profinet side: No. | Sub-models: -CAN, -COM, -COS, -MRTUM, -MRTUS, -MTCPS, -PROG. | 2× Profinet, 1× CAN, 1× RS485, 1× Ethernet (varies) |
Siemens PLC integrating CANopen drives; active CANopen network management. | |
| • -CAN: Raw passthrough. | • -CAN: Passthrough | CAN side: NO | |||||
| • -COM: CANopen Slave. | • -COM: CANopen Slave | CAN side: NO | |||||
| • -COS: CANopen Master (NMT, node monitoring). | • -COS: CANopen Master | CAN side: -COS YES | |||||
| • -PROG: Programmable. | User-defined (Master/Slave configurable) | Yes (Configurable via program) | |||||
| GCAN-GT-415 | Full programmable semantic processing. | Configurable via program | Yes, fully configurable. CANopen & Modbus Master/Slave. | No fixed sub-models. Programmable via OpenPCS (IEC 61131-3). | 2× CAN, Ethernet, RS485, RS232, 4G, WiFi | Multi-protocol mixing, non-standard logic, remote upload (acts as a mini-PLC). |
GCAN-204 Technical FAQ: Modbus RTU Slave to CAN Integration & Troubleshooting
Q Can GCAN-204 function as a Modbus RTU Master? ▼
No. The GCAN-204 is strictly a Modbus RTU Slave device. It cannot actively poll or manage other Modbus devices. It is designed to wait for read/write requests from an existing Modbus Master (such as a PLC, HMI, or SCADA system) and translate those requests into CAN frames.
(If you need a gateway to actively poll Modbus devices or act as a CANopen Master, please refer to our Level 4 or Level 5 gateways.)
Q How does the Zero-Coding CAN-to-Register Mapping work? ▼
Unlike basic passthrough gateways that just move raw data, the GCAN-204 operates at Level 3 (Register Mapping). It extracts the payload from specific CAN IDs and maps them directly into standard Modbus registers.
Using our free configuration software, you simply define which CAN ID corresponds to which register address. Your PLC can then read the data directly using standard Modbus function codes (03H, 04H, 06H, 16H) without writing any host-side parsing code.
Q Why does my PLC read raw Hex data instead of a physical value (e.g., 25.5°C)? ▼
Because gateways handle protocol-level semantics, not physical quantity semantics. The GCAN-204 accurately translates the byte structure from the CAN frame into the Modbus register, but it does not know if the raw data represents temperature, RPM, or voltage.
The physical scaling and engineering units (e.g., dividing by 100 to get 25.5°C) must be configured inside your upper-level system (PLC or HMI).
Q Do I need a 120Ω termination resistor for the CAN bus? ▼
Yes. A standard CAN bus requires exactly two 120Ω terminal resistors, installed at the two furthest physical ends of the bus (connected between CAN_H and CAN_L). Without them, signal reflections will occur, leading to data loss, error frames, and unstable communication—especially at higher baud rates (e.g., 500 Kbps or 1 Mbps).
Q What is the Maximum Data Conversion Throughput (fps)? ▼
The GCAN-204 supports a maximum data conversion rate of 400 frames per second (fps) per CAN channel. This maximum rate is achieved when the RS485 serial baud rate is set to 115200 bps. This throughput is highly sufficient for standard industrial data acquisition, parameter monitoring, and control command delivery.